ORION

Conventional Fire Detection Panel

The ORION range of conventional control panels features three models with 2, 4 and 8 zones of detection. Housed in a stylish modern ABS housing, the ORION is the ideal control panel for smaller installations.

Designed and manufactured to comply with the requirements of EN54 parts 2 and 4 (1998), the ORION uses active end of line monitoring to permit head removal protection as required by BS5839 (detector bases must be fitted with diode).

Programmable zone coincidence and alarm delay timer (0-10 min) are standard features to help reduce false alarms.

The one-man test facility enables simple and rapid testing of the system during commissioning and maintenance operations.

Add to quote

Product Features

  • 2, 4 and 8 Zone non-expandable control panels
  • Up to 32 conventional smoke and/or heat detectors per Zone
  • Active End of Line monitoring
  • Programmable non-latching Zones
  • Delay timer programmable on/off per Zone
  • Coincidence programmable for adjacent Zones
  • One man test
  • Supervised auxiliary 24 volt output
  • 2 Supervised/ monitored sounder circuits
  • 3 Remote inputs used for activation of Class Change, Day/Night mode, and Reset
  • 2 Relay outputs fire and fault
  • Fully EN54 part 2 and 4 compliant
  • Repeater output
  • Multiplexed output for LEDs and additional relay outputs per zone (GFE-MPX-REL)
  • Multiplexed output for sounders per zone (GFE-MPX-SNDR)
  • Addressable Loop Interface card (GFE-ADLI)

Product Specifications

Additional information

Primary Supply Voltage - In

230V AC +10% -15%

Primary Supply Voltage - Out

28.5V DC nominal

Primary Supply Current - Out

1.7A @ 28.5V DC nominal (max.)

Secondary Supply Voltage

21.0 min. – 27.2 max. V DC – BAT charger o/p 28V DC

Secondary Supply Current Output

1.85 Amp maximum @ 20 o C

Internal Battery Capacity - Max

2 x 12V x 7Ah Sealed VRLA Lead Acid Batteries

Mains Fuse

4 A 250 V Slow Blow – 20 mm

Battery Fuse

1.85 Amp – Resettable

Number Of Detection Zones

2 / 4 / 8

Zone Current - Quiescent / Alarm

10 mA / 60 mA maximum

Max Cable Resistance / Capacitance

40 Ohms / 0.470 uF

End Of Line Monitoring

Active EOL – 10uF/50V Bipolar Capacitor

BS-5839 Detector Removal Compliant

YES provided diodes are fitted to detector base

Devices Per Zone

32 maximum – EN54 pt.2

Alarm Resistance Value: Inputs

270 – 1000 Ohms

Max Current: Outputs

1,85A maximum current drive for both S1 & S2 circuits; 100 mA for RM output

Voltage Output

27.5V DC nominal

Auxiliary Relay Output

1 Fire (COM-NC-NO) – 1 Fault (COM-NC) non-supervised

Relay Contact Rating

30V DC – 2A / 230V AC – 0.25A (resistive loads)

Evacuation And Reset

Non-Latching – Voltage free contact

Max Humidity

95% RH Non-Condensing

Protection Rating

IP30

Operating Temperature

-10ºC to 50ºC

Weight

1.7 Kg – 7 Kg (inc. 2 x 7 AH 12 V bat.)

Dimensions

273 (L) x 107 (W) x 404 (H) mm

Colour

White or Red

Download Centre

Add to quote