ORION-PLUS

Expandable Conventional Fire Detection Panel

The ORION + range of expandable conventional control panels offers an aesthetically pleasing and functional cabinet design for larger projects demanding ease of installation and commissioning, as well as simple operation, such as conventional installations.

The unit can be expanded easily from eight to 16 zones by installing additional modules with four zones. The range also includes two types of repeater.

The outstanding programming features included in this panel range exceed the possibilities of standard conventional panels, using a graphic LCD display and real time clock which permits the recording of events in a time stamped log.

Operation is intuitive, offering simple control and one-button disablement facilities, as well as a one-man test routine, which provides a highly effective way to perform regular testing of the fire alarm system.

Advanced configuration interfacing includes RS232, RS422/485, fibre optic, GSM-GPRS and TCP/IP. All of the above make use of our own proprietary interfaces.

Add to quote

Product Specifications

Additional information

Primary Supply Voltage - In

90 to 265 V AC

Primary Supply Voltage - Out

28.5 V DC nominal

Primary Supply Current - Out

1.7 A @ 28.5 V DC nominal (max.)

Secondary Supply Voltage

21.0 min. – 27.2 max. V DC – BAT charger o/p 28 V DC

Secondary Supply Current Output

1.1 Amp Maximum @ 20ºC

Internal Battery Capacity - Max

2 x 12 V x 7 Ah Sealed VRLA Lead Acid Batteries

Mains Fuse

4 A -250 V Slow Blow – 20 mm

Battery Fuse

1.6 Amp – Resettable

Number Of Circuits

16 Max.

Zone Current - Quiescent / Alarm

4 mA / 60 mA – Maximum

Max Cable Resistance / Capacitance

40 Ohms / 0.470 uF

End Of Line Monitoring

Active EOL – 10uF/50V Bipolar Electrolytic Aluminium Capacitor

BS-5839 Detector Removal Compliant

YES (provided diodes are fitted to detector base)

Devices Per Zone

32 Maximum – EN54 pt.2

Alarm Resistance Value

270 – 1000 Ohms

Current Output

2 outputs w/ 500 mA max. current drive per circuit – fully monitored

Alarm Voltage / End Of Line Resistor

27.5 V DC Nominal / 10 K Ohms – 1/4 Watt

Auxiliary Relay Output

1 Fire (COM-NC-NO) – 1 Fault (COM-NC) non-supervised

Relay Contact Rating

50 V DC – 1 Amp resistive loads

Programmable Input 1 / Input 2

Non-Latching – Voltage free contact / Non-Latching – Voltage free contact

Humidity

Max 95% RH Non-Condensing

Operating Temperature

-10ºC to 50ºC

Weight (Orion-Plus)

2 Kg without batteries, 7 Kg with batteries (2 x 12 V x 7Ah)

Dimensions (Orion Plus)

273 (L) x 107 (W) x 404 (H) mm

Colour

White or Red

Download Centre