ORION-EX V2

Conventional Fire Detection & Extinguishing Panel

The ORION-EX conventional fire detection and extinguishing panel offers a creatively designed and aesthetically pleasing solution to satisfy the increasing global demand for dependable fire suppression systems. The ORION-EX is designed and manufactured to comply with EN54-2, EN54-4 and EN12094-1 standards.

The outstanding programmable features included in this panel are best suited to installation in high value housing areas and, more generally, in any areas where loss of equipment can partially or totally disrupt the proper functioning of a business.

Operation is extremely intuitive, offering simple control and one-button disablement facilities, as well as the one man test mode which provides simple and efficient testing of the system.

Add to quote

Product Features

  • 4 Fire Detection Zones: 2 crossed Zones and 1 individual Zone linked with automatic extinguishing cycle; 1 Zone dedicated only for fire detection which doesn’t activates automatic extinguishing cycle
  • Up to 32 conventional devices (smoke and/or heat detectors and call-points) per zone
  • Active End of Line for Zone wiring monitoring (10uF/50V bipolar capacitor)
  • Programmable Pre-Release and Extinguishing times
  • Monitored inputs for Manual Extinguishing Cycle Activation and Remote Abort
  • Electrovalve solenoid and Weight/Flow/Pressure Switch Status monitoring
  • Supervised auxiliary 24-volt supply output
  • 3 Supervised/monitored output circuits
  • 1 Remote reset input
  • 2 Relay outputs for fire and fault status indication
  • Dedicated repeater panel and analogue loop interface
  • Additional outputs via MPX-REL & MPX-SNDR modules
  • EN54-2, EN54-4 and EN12094-1 fully compliant

Product Specifications

Additional information

Primary Supply Voltage - In

230V AC +10% -15%

Primary Supply Voltage - Out

28.5V DC nominal

Primary Supply Current - Out

1.7A @ 28.5V DC nominal (max.)

Secondary Supply Voltage

21.0 min. – 27.2 max. V DC – BAT charger o/p 28V DC

Secondary Supply Current Output

1.85 Amp maximum @ 20 o C

Internal Battery Capacity - Max

2 x 12V x 7Ah Sealed VRLA Lead Acid Batteries

Mains Fuse

4 A 250 V Slow Blow – 20 mm

Battery Fuse

1.85 Amp – Resettable

Number Of Detection Zones

4

Zone Current - Quiescent / Alarm

10 mA / 60 mA maximum

Max Cable Resistance/Capacitance

40 Ohms / 0.470 uF

End Of Line Monitoring

Active EOL – 10uF/50V Bipolar Capacitor

BS-5839 Detector Removal Compliant

YES provided diodes are fitted to detector base

Devices Per Zone

32 maximum – EN54 pt.2

Alarm Resistance Value: Inputs

270 – 1000 Ohms

Max Current: Outputs

1,85A maximum current drive for both S1 & S2 circuits; 100 mA for RM output

Voltage Output

27.5V DC nominal

Auxiliary Relay Output

1 Fire (COM-NC-NO) – 1 Fault (COM-NC) non-supervised

Relay Contact Rating

30V DC – 2A / 230V AC – 0.25A (resistive loads)

Fully Monitored Inputs

Remote Activation, Remote Abort, Solenoid Status, Flow/Pressure Switch Status

Evacuation And Reset

Non-Latching – Voltage free contact

Max Humidity

95% RH Non-Condensing

Protection Rating

IP30

Operating Temperature

-10ºC to 50ºC

Weight

1.7 Kg – 7 Kg (inc. 2 x 7 AH 12 V bat.)

Dimensions

273 (L) x 107 (W) x 404 (H) mm

Colour

White or Red

Download Centre

Add to quote