The ZEOS-AS series of Analogue Addressable Detectors have been designed to be fully compatible with Global Fire Equipment’s range of intelligent control panels, JUNIOR and JUNO NET.
The ZEOS detector range, in conjunction with JUNIOR and JUNO NET panels, can accommodate several Alarm
thresholds and timed options in combined smoke and heat detectors variants.
The ZEOS-AS series is certified to EN54-5 and EN54-7 and consists of combined photoelectric smoke and heat
detectors. Optionally they can be fitted with a short-circuit loop isolator.
The ZEOS-AS range of fire detectors is not addressed using a D.I.L. switch, it uses instead GFE’s proprietary Smart
Addressing Mechanism (SAM). The address can be set either by using GFE’s analogue device programmer or
alternatively, when used in conjunction with GFE’s range of Intelligent Analogue Addressable Fire Detection Panels,
GFE’s automatic address setting mode ASET.
Supply Voltage | Loop Powered 17-30 V DC |
---|---|
Current - Quiescent / Surge | 450 uA max. |
Current - Device In Alarm | 4 mA – Alarm LED illuminated |
Sensitivity | According to EN54-5 or/and EN54-7, EN54-17 |
Cable Size | 0.5-2.5 mm² |
Reset / Startup Times | 20 seconds max. |
Smoke Sensitivity Settings | Low / Normal (default) / High |
Heat Alarm Setpoints | 55 C / 65 C (default) / 75 C / 85 C |
Multisensor Modes | Heat / Smoke / Combined (default) |
Colour / Case Material | White / ABS |
Normal / Transient Operation Temperature | 0ºC to 50ºC / -10ºC to 85ºC |
Max. Humidity | 95% RH Non-Condensing |
Dimensions | 100 (D) x 50 (H) mm inc. base |
Weight | 92 g (without base) & 144 g (inc. base) |